Softening or antiscalant? Scale control before RO
Summary

In the reverse osmosis concentrate, salts are concentrated 2–4 times; when calcium carbonate and sulphate reach saturation, they precipitate on the membrane surface. There are two ways to prevent this.

Softening (ion exchange)

  • Removes hardness completely; the risk of scaling drops to zero and recovery can rise to 75–80%.
  • Higher investment, salt consumption and brine waste.
  • If iron/manganese is present, prefiltration is needed to protect the resin.
  • Not used for water with high conductivity and salinity; in such water, scale is controlled with an antiscalant.

Antiscalant dosing

  • Low investment; a small dosing pump and chemical tank are enough.
  • The hardness stays in the water; the dose calculation depends on the water analysis, and scaling begins at the wrong dose.
  • On its own, it may be insufficient with silica and very high hardness (> 40 °fH).
  • The preferred method for water with high conductivity and salinity; softening is not used for such water.

Decision table

SituationRecommendation
High conductivity and salinityAntiscalant (softening is not used)
Hardness < 25 °fH, low silica, 60–70% recoveryAntiscalant
Hardness > 30 °fH or a high recovery targetSoftening (+ antiscalant if necessary)
Product water to be used in a boilerSoftening (the boiler is also protected from scale)
Small capacity (< 1 m³/h), low hardnessAntiscalant or cartridge polyphosphate

In medium and large industrial systems, the safest arrangement is softening + a low dose of antiscalant; for water with high conductivity and salinity, softening is not used and scale control is provided by an antiscalant. For the resin volume, see the softener calculator.